7.4.4.48 Pset_ProtectiveDeviceOccurrence

PSET_OCCURRENCEDRIVEN / IfcProtectiveDevice

Natural language names
Protective Device Occurrence
Properties

buildingSMART Data Dictionary

PSD-XML

NameTypeDescription
PoleUsage P_ENUMERATEDVALUE / IfcLabel / PEnum_PoleUsage
Pole UsagePole usage.
LongTimeFunction P_SINGLEVALUE / IfcBoolean
Long Time FunctionApplying long time function A flag indicating that the long time function (i.e. the thermal tripping) of the device is used. The value should be set to TRUE for all devices except those that allows the Long time function of the device not to be used.
ShortTimeFunction P_SINGLEVALUE / IfcBoolean
Short Time FunctionApplying short time function A flag indicating that the short time function of the device is used. The value should be set to FALSE for devices not having a short time function, or if the short time function is not selected to be used.
ShortTimei2tFunction P_SINGLEVALUE / IfcBoolean
Short Timei2t FunctionApplying short time i2t function. A flag indicating that the I2t short time function of the device is used. The value should be set to TRUE only if the I2t function 聽is explicitly selected for the device.
GroundFaultFunction P_SINGLEVALUE / IfcBoolean
Ground Fault FunctionApplying ground fault function. A flag indicating that the ground fault function of the device is used. The value should be set to FALSE for devices not having a ground fault function, or if the ground fault function is not selected to be used.
GroundFaulti2tFunction P_SINGLEVALUE / IfcBoolean
Ground Faulti2t FunctionApplying ground fault i2t function. A flag indicating that the I2t ground fault function of the device is used. The value should be set to TRUE only if the I2t function is explicitly selected for the device.
LongTimeCurrentSetValue P_SINGLEVALUE / IfcElectricCurrentMeasure
Long Time Current Set ValueLong time current set value. The set value of the long time tripping current if adjustable.
ShortTimeCurrentSetValue P_SINGLEVALUE / IfcElectricCurrentMeasure
Short Time Current Set ValueShort time current set value. The set value of the long time tripping current if adjustable.
InstantaneousCurrentSetValue P_SINGLEVALUE / IfcElectricCurrentMeasure
Instantaneous Current Set ValueInstantaneous current set value. The set value of the instantaneous tripping current if adjustable.
GroundFaultCurrentSetValue P_SINGLEVALUE / IfcElectricCurrentMeasure
Ground Fault Current Set ValueGround fault current set value. The set value of the ground tripping current if adjustable.
LongTimeDelay P_SINGLEVALUE / IfcTimeMeasure
Long Time DelayLong time delay. The set value of the long time time-delay if adjustable.
ShortTimeTrippingTime P_SINGLEVALUE / IfcTimeMeasure
Short Time Tripping TimeShort time tripping time. The set value of the short time tripping time if adjustable.
InstantaneousTrippingTime P_SINGLEVALUE / IfcTimeMeasure
Instantaneous Tripping TimeInstantaneous tripping time. The set value of the instantaneous tripping time if adjustable.
GroundFaultTrippingTime P_SINGLEVALUE / IfcTimeMeasure
Ground Fault Tripping TimeGround fault tripping time. The set value of the ground fault tripping current if adjustable.